Project settings
These settings change the limits used everywhere else. Sprinkler status in particular changes common path, travel distance, exit separation, dead ends and finish classes, so confirm it before you trust any result.
Identification
Classification and protection
Calculation assumptions
Assumptions and open items
Your work is kept in this browser only, in the workspace you chose. Use the Summary tab to download a copy you can submit or reopen on another computer.
Lecture: Determining Building Codes for Interior Design
The lecture this calculator follows, 46 slides, 2021 IBC. Use the index to jump to a slide; the case study in the Program tab is the building worked in slides 19 to 21, 26 to 31, 35, 38 and 40. If the viewer stays blank in your browser, open the lecture in a new tab or download it.
Program components and occupant load
One row per space type. Choose the function of space: it sets the factor and whether the area is net or gross (Table 1004.5). The tool proposes an occupancy group and says why; override it only with a code reason, and write that reason in your study.
Stories: exits, separation, travel limits, widths
Enter each floor plate’s length, width and gross area. The occupant load is summed from the Program tab. Exits per story follow Table 1006.3.3; each story is judged on its own load (1006.3.1). The limits shown are what you must then measure against on your plan. Lecture, slides 26 to 30.
Plan measurements
Upload a plan image for a story (a PNG or JPG exported from your drawing), set the scale first by clicking the two ends of a known dimension and typing its length, then draw the longest diagonal of the floor (two opposite corners), the straight line between the two exit doors, and the longest travel path. Nothing converts to feet until the scale is set. Each measurement is compared with the limit from the Stories tab and written into the Summary. If you have no digital plan, type the values you measured by hand; the Summary marks them as typed.
The image stays in this browser session only; your points, scale and measurements are saved with the project. Upload the same image again to see the drawing after reopening.
Exit calculators
Two quick calculators with the arithmetic shown. Use them for a floor or a room you have not entered in the Program, or to check a number by hand. Both read the sprinkler setting from the Project tab unless you change it here.
Floor: how many exits, and how far apart
Room: one door or two, and how far apart
Plumbing fixtures (Table 2902.1)
Occupants are grouped by the Table 2902.1 row that matches their classification, split in half between the sexes with each half rounded up (2902.1.1), and the ratios applied per sex. Drinking fountains and service sinks use the whole load. Lecture, slides 36 to 38.
Interior wall and ceiling finishes (Table 803.13)
Class A: flame spread index 0 to 25. Class B: 26 to 75. Class C: 76 to 200. All three require a smoke-developed index of 0 to 450 (803.1.2, ASTM E84 or UL 723). The sprinkler setting selects the column set. Lecture, slides 39 and 40.
Practice problems
Fifteen short problems on the steps you just worked through. Answer each one, then read the explanation and its reference. Your score is kept in this browser; reset to try again.
Summary and export
The eight blocks of your preliminary code study, with references. Add your plan diagram (exits, diagonal D, separation, longest travel path and its common-path portion, two-door rooms) when you submit.