Preliminary code study calculator

2021 International Building Code. Enter your program, read the result and the reason beside it, then check the limits on your plan. Companion to the lecture Determining Building Codes for Interior Design.

Project settings

These settings change the limits used everywhere else. Sprinkler status in particular changes common path, travel distance, exit separation, dead ends and finish classes, so confirm it before you trust any result.

Identification

The city, county or state that adopted the code. Record the ordinance numbers in your study.
This tool follows the 2021 IBC table numbers. Other editions number several tables differently.

Classification and protection

Rooms that serve the main occupancy (accessory storage, mechanical rooms) are assigned to this group (311.1.1, 509). Story-level travel and dead-end limits use it.
Partial systems do not qualify. For an existing building, verify on site and write how you know in the assumptions.

Calculation assumptions

Applied to net-factor spaces when no measured net area is entered. The code excludes corridors, stairs, toilet rooms, mechanical rooms and closets from net floor area (Chapter 2). Replace with measured areas in the design phase.
0.3 per 1005.3.1; 0.2 only with sprinklers plus an emergency voice/alarm system (not Groups H and I-2).
0.2 per 1005.3.2 for doors, corridors and ramps; 0.15 with sprinklers plus emergency voice/alarm.

Assumptions and open items

Your work is kept in this browser only, in the workspace you chose. Use the Summary tab to download a copy you can submit or reopen on another computer.